General Technical Information
| Standard dimension L x W | 2440 x 1220 mm |
| Thickness | 9,12,15 & 24 mm |
| Density | 950 kg/m3 |
| Thermal conductivity (k) at mean temperature | ≤ 0.20 W/mk |
| Moisture content | ≤ 10% |
| Combustibility | Non combustable to BS476: Pt 4 : 1970 |
| Fire propagation | Index(I) to BS476 : Pt 6 : 1969 |
| Surface spread of flame | Class 1 to BS 476: Pt 7 : 1987 |
| Thickness tolerance of standard boards | ± 0.5 mm |
| Length x width tolerance of standard boards | -0, +4 mm |
| Asbestos | 100% free |
Certification
The Ingeborg® system has been tested in accordance to international standards BS 476: Pt 24 and AS 1530.4. This test was conducted in an accredited lab based in New Zealand registered under the BRANZ group.
For use in Singapore, we have undergone tests to meet the stringent requirements of SCDF regulated products. Our product has also obtained approval and certification by an independent international body, TÜV SÜD PSB, and is listed in their Product Listing Scheme (PLS) Class 1A. This scheme entails safety and performance testing of products in accordance to the international standards. Products listed in the PLS will be granted a Certificate of Conformity (COC) by PSB.
Recommended Applications
- Mechanical Ventilation System
- Smoke Extraction System
- Kitchen Exhaust System
- Dual Ventilation/Smoke Extract System
Services
We provide construction detail of our system for your installation when you purchase Ingeborg®. We will provide surveillance inspection upon your successful installation of the system. A site audit report will then be submitted to PSB for approval prior to issuance of the Declaration of Compliance (DOC). The DOC is a project based document that is given to each individual project.
Find out more by downloading our brochure here. Back
Fire testing of the Ingeborg® system